Pseudomonads in a university

Cleaning the drinking water installation due to contamination with pseudomonads
The customer order

Task

  • Eliminate contamination with Pseudomonas aeruginosa
  • Cause: improper filter change
  • Cleaning cold water pipes with the Comprex® process
  • Eliminate turbidity problems
  • Cleaning measures to avoid business interruptions only possible at weekends in some cases

Technical data

  • Cleaning measures to avoid business interruptions only possible at weekends in some cases
  • Year of construction of the building complex: 1955/56
  • Age of the drinking water installation: 1 to 3 years

7 working days

430 cold water taps

Comprex® cleaning

Implementation

  • mechanical cleaning with air and drinking water
  • Provision of compressed, conditioned air by Comprex® unit
  • Access to the system via adapter connections
  • Bundled discharge of several tapping points by means of a special cyclone separator
  • cleaning up to each tap line by line

Elimination of pseudomonads in a college

Our services in facts and figures

Comprex® - unit
TI EMERGENCY VEHICLE
TECHNICIAN
Download

The practical example as PDF

Result of Comprex® cleaning

Elimination of pseudomonads through Comprex® purification

  • Deposits as well as biofilms mobilized and discharged
  • Pseudomonas concentration < 0 CFU/100 ml
  • Turbidity no longer present
What makes our solution stand out:
With our Comprex® air-water impulse cleaning system, we provide an effective, sustainable, and resource-efficient cleaning solution.
Do you have any questions? We’re happy to help you find the right solution with Comprex®

Posts that might also interest you

The prerequisite for the commissioning of the drinking water installation are tightness and hygienic condition
20261013
Cleaning the cooling channels of two injection molds at a manufacturer of plastic components for shoes
20261013
Scroll to Top
Contact form

Thank you for your interest in our Comprex® process

Please note our privacy policy.